EPRN
Products
EPRN
600V~15kV EPR (Ethylene Propylene Rubber) Insulated Neoprene Sheathed Power Cables (EPRN). It is used at wiring for power and equipment. It shall comply with the standards of ICEA.
Features
Construction:(1) Conductor: tinned or untinned soft annealed stranded copper wires (2) Conductor screen (voltage >2001V) (3) Insulation: EPR (4) Insulation screen (voltage > 2001V) (5) Tinned copper tape shielding (voltage > 2001V) (6) Two or more cores are twisted together,cable core covered with proper separator (7) Sheath: Neoprene Introduction: The EPRN power Cable is used for power distribution system. The EPR insulated Neoprene (Polyvinyl Chloride) sheathed power cable has excellent insulation resistance. It can withstand impact, bending, abrasion, elongation etc.. It has excellent oil-resistant and chemical-resistant properties. It has excellent heat-resistant, weatherproof properties. ICEA: The Insulated Cable Engineers Association.
Specifications
600V EPRN Single Core Power Cable Refer To ICEA
Conductor | Thickness of insulation mm | Approx. Overall Diameter mm | Approx. Weight Kg/km | Standard Length M | ||
Normative Cross Area AWGorMCM | Number/ Diameter of Wires No./mm | Outer Diameter Approx. mm | ||||
14 | 7/0.615 | 1.85 | 1.14 | 6.5 | 48 | 300 |
13 | 7/0.691 | 2.08 | 1.14 | 6.5 | 57 | 300 |
12 | 7/0.779 | 2.34 | 1.14 | 7.0 | 65 | 300 |
11 | 7/0.871 | 2.62 | 1.14 | 7.5 | 80 | 300 |
10 | 7/0.978 | 2.95 | 1.14 | 7.5 | 87 | 300 |
9 | 7/1.1 | 3.30 | 1.14 | 8.0 | 102 | 300 |
8 | 7/1.23 | 3.70 | 1.52 | 9.0 | 137 | 300 |
7 | 7/1.39 | 4.16 | 1.52 | 10.0 | 173 | 300 |
6 | 7/1.56 | 4.67 | 1.52 | 10.5 | 203 | 300 |
5 | 7/1.75 | 5.24 | 1.52 | 11 | 240 | 300 |
4 | 7/1.95 | 5.88 | 1.52 | 12 | 286 | 300 |
3 | 7/2.2 | 6.61 | 1.52 | 13.5 | 343 | 300 |
2 | 7/2.47 | 7.42 | 1.52 | 14.0 | 414 | 300 |
1 | 19/1.69 | 8.43 | 2.03 | 15.5 | 550 | 300 |
1/0 | 19/1.89 | 9.46 | 2.03 | 16.5 | 664 | 300 |
2/0 | 19/2.13 | 10.6 | 2.03 | 18 | 805 | 300 |
3/0 | 19/2.39 | 11.9 | 2.03 | 20 | 983 | 300 |
4/0 | 19/2.68 | 13.4 | 2.03 | 21 | 1203 | 300 |
250 | 37/2.09 | 14.6 | 2.41 | 25.5 | 1503 | 300 |
300 | 37/2.29 | 16.1 | 2.41 | 26.5 | 1760 | 300 |
350 | 37/2.47 | 17.3 | 2.41 | 29 | 2010 | 300 |
400 | 37/2.64 | 18.5 | 2.41 | 30 | 2260 | 300 |
450 | 37/2.8 | 19.6 | 2.41 | 31 | 2509 | 300 |
500 | 37/2.95 | 20.7 | 2.41 | 32 | 2758 | 200 |
550 | 61/2.41 | 21.7 | 2.79 | 34 | 3060 | 200 |
600 | 61/2.52 | 22.7 | 2.79 | 35 | 3308 | 200 |
650 | 61/2.6 | 23.6 | 2.79 | 36 | 3555 | 200 |
700 | 61/2.72 | 24.5 | 2.79 | 37 | 3802 | 200 |
750 | 61/2.82 | 25.3 | 2.79 | 39 | 4047 | 200 |
800 | 61/2.91 | 26.2 | 2.79 | 40 | 4293 | 200 |
600V EPRN Two Core Power Cable Refer To ICEA
Conductor | Thickness of insulation mm | Approx. Overall Diameter mm | Approx. Weight Kg/km | Standard Length M | ||
Normative Cross Area AWGorMCM | Number/ Diameter of Wires No./mm | Outer Diameter Approx. mm | ||||
14 | 7/0.615 | 1.85 | 1.14 | 14 | 150 | 300 |
13 | 7/0.691 | 2.08 | 1.14 | 14.5 | 170 | 300 |
12 | 7/0.779 | 2.34 | 1.14 | 15.5 | 206 | 300 |
11 | 7/0.871 | 2.62 | 1.14 | 16.5 | 239 | 300 |
10 | 7/0.978 | 2.95 | 1.14 | 17.0 | 258 | 300 |
9 | 7/1.1 | 3.30 | 1.14 | 17.5 | 293 | 300 |
8 | 7/1.23 | 3.70 | 1.52 | 22 | 420 | 300 |
7 | 7/1.39 | 4.16 | 1.52 | 24 | 513 | 300 |
6 | 7/1.56 | 4.67 | 1.52 | 25.5 | 583 | 300 |
5 | 7/1.75 | 5.24 | 1.52 | 26 | 667 | 300 |
4 | 7/1.95 | 5.88 | 1.52 | 29 | 772 | 300 |
3 | 7/2.2 | 6.61 | 1.52 | 30 | 900 | 300 |
2 | 7/2.47 | 7.42 | 1.52 | 32 | 1057 | 300 |
1 | 19/1.69 | 8.43 | 2.03 | 34 | 1304 | 300 |
1/0 | 19/1.89 | 9.46 | 2.03 | 36 | 1548 | 300 |
2/0 | 19/2.13 | 10.6 | 2.03 | 39 | 1848 | 200 |
3/0 | 19/2.39 | 11.9 | 2.03 | 42 | 2234 | 200 |
4/0 | 19/2.68 | 13.4 | 2.03 | 45 | 2689 | 200 |
250 | 37/2.09 | 14.6 | 2.41 | 53 | 3363 | 200 |
300 | 37/2.29 | 16.1 | 2.41 | 56 | 3902 | 200 |
350 | 37/2.47 | 17.3 | 2.41 | 58 | 4423 | 200 |
400 | 37/2.64 | 18.5 | 2.41 | 61 | 4946 | 200 |
450 | 37/2.8 | 19.6 | 2.41 | 63 | 5463 | 200 |
500 | 37/2.95 | 20.7 | 2.41 | 66 | 5955 | 200 |
550 | 61/2.41 | 21.7 | 2.79 | 70 | 6616 | 200 |
600 | 61/2.52 | 22.7 | 2.79 | 72 | 7130 | 200 |
650 | 61/2.6 | 23.6 | 2.79 | 74 | 7640 | 200 |
700 | 61/2.72 | 24.5 | 2.79 | 78 | 8350 | 200 |
750 | 61/2.82 | 25.3 | 2.79 | 79 | 8859 | 200 |
800 | 61/2.91 | 26.2 | 2.79 | 81 | 9417 | 200 |
600V EPRN Three Core Power Cable Refer To ICEA
Conductor | Thickness of insulation mm | Approx. Overall Diameter mm | Approx. Weight Kg/km | Standard Length M | ||
Normative Cross Area AWGorMCM | Number/ Diameter of Wires No./mm | Outer Diameter Approx. mm | ||||
14 | 7/0.615 | 1.85 | 1.14 | 15.5 | 253 | 300 |
13 | 7/0.691 | 2.08 | 1.14 | 16 | 288 | 300 |
12 | 7/0.779 | 2.34 | 1.14 | 16.5 | 320 | 300 |
11 | 7/0.871 | 2.62 | 1.14 | 17 | 373 | 300 |
10 | 7/0.978 | 2.95 | 1.14 | 17.5 | 406 | 300 |
9 | 7/1.1 | 3.30 | 1.14 | 19 | 464 | 300 |
8 | 7/1.23 | 3.70 | 1.52 | 23 | 729 | 300 |
7 | 7/1.39 | 4.16 | 1.52 | 24 | 826 | 300 |
6 | 7/1.56 | 4.67 | 1.52 | 26 | 943 | 300 |
5 | 7/1.75 | 5.24 | 1.52 | 28 | 1083 | 300 |
4 | 7/1.95 | 5.88 | 1.52 | 29 | 1258 | 300 |
3 | 7/2.2 | 6.61 | 1.52 | 31 | 1472 | 300 |
2 | 7/2.47 | 7.42 | 1.52 | 32 | 1734 | 300 |
1 | 19/1.69 | 8.43 | 2.03 | 35 | 2141 | 300 |
1/0 | 19/1.89 | 9.46 | 2.03 | 37 | 2548 | 300 |
2/0 | 19/2.13 | 10.6 | 2.03 | 40 | 3049 | 200 |
3/0 | 19/2.39 | 11.9 | 2.03 | 43 | 3674 | 200 |
4/0 | 19/2.68 | 13.4 | 2.03 | 50 | 4575 | 200 |
250 | 37/2.09 | 14.6 | 2.41 | 56 | 5590 | 200 |
300 | 37/2.29 | 16.1 | 2.41 | 61 | 6498 | 200 |
350 | 37/2.47 | 17.3 | 2.41 | 63 | 7367 | 200 |
400 | 37/2.64 | 18.5 | 2.41 | 66 | 8241 | 200 |
450 | 37/2.8 | 19.6 | 2.41 | 68 | 9105 | 200 |
500 | 37/2.95 | 20.7 | 2.41 | 70 | 9973 | 200 |
550 | 61/2.41 | 21.7 | 2.79 | 74 | 11084 | 200 |
600 | 61/2.52 | 22.7 | 2.79 | 79 | 12155 | 200 |
650 | 61/2.6 | 23.6 | 2.79 | 81 | 13013 | 200 |
700 | 61/2.72 | 24.5 | 2.79 | 83 | 13874 | 200 |
750 | 61/2.82 | 25.3 | 2.79 | 86 | 14719 | 200 |
800 | 61/2.91 | 26.2 | 2.79 | 87 | 15585 | 200 |
5KV EPRN Single Core Power Cable Refer to ICEA
Conductor | Thickness of | Approx. | Standard | ||
Normative | Number/ | Outer | |||
AWGorMCM | No./mm | mm | mm | mm | M |
008 | 07/1.23 | 03.70 | 2.29 | 13.0 | 300 |
007 | 07/1.39 | 04.16 | 2.29 | 14.0 | 300 |
006 | 07/1.56 | 04.67 | 2.29 | 14.5 | 300 |
005 | 07/1.75 | 05.24 | 2.29 | 15.0 | 300 |
004 | 07/1.95 | 05.88 | 2.29 | 15.5 | 300 |
003 | 07/2.20 | 06.61 | 2.29 | 17.5 | 300 |
002 | 07/2.47 | 07.42 | 2.29 | 19.0 | 300 |
001 | 19/1.69 | 08.43 | 2.29 | 20.0 | 300 |
1/0 | 19/1.89 | 09.46 | 2.29 | 21.0 | 300 |
2/0 | 19/2.13 | 10.60 | 2.29 | 22.0 | 300 |
3/0 | 19/2.39 | 11.90 | 2.29 | 23.0 | 300 |
4/0 | 19/2.68 | 13.40 | 2.29 | 25.0 | 300 |
250 | 37/2.09 | 14.60 | 2.29 | 28.0 | 300 |
300 | 37/2.29 | 16.10 | 2.29 | 29.0 | 300 |
350 | 37/2.47 | 17.30 | 2.29 | 31.0 | 300 |
400 | 37/2.64 | 18.50 | 2.29 | 32.0 | 300 |
450 | 37/2.80 | 19.60 | 2.29 | 33.0 | 300 |
500 | 37/2.95 | 20.70 | 2.29 | 34.0 | 200 |
550 | 61/2.41 | 21.70 | 2.29 | 35.0 | 200 |
600 | 61/2.52 | 22.70 | 2.29 | 36.0 | 200 |
650 | 61/2.62 | 23.60 | 2.29 | 37.0 | 200 |
700 | 61/2.72 | 24.50 | 2.29 | 38.0 | 200 |
750 | 61/2.82 | 25.30 | 2.29 | 39.0 | 200 |
800 | 61/2.91 | 26.20 | 2.29 | 41.0 | 200 |
5KV EPRN Two Cores Power Cable Refer to ICEA
Conductor | Thickness of | Approx. | Standard | ||
Normative | Number/ | Outer | |||
AWGorMCM | No./mm | mm | mm | mm | M |
008 | 07/1.23 | 03.70 | 2.29 | 26.0 | 300 |
007 | 07/1.39 | 04.16 | 2.29 | 27.5 | 300 |
006 | 07/1.56 | 04.67 | 2.29 | 28.0 | 300 |
005 | 07/1.75 | 05.24 | 2.29 | 30.0 | 300 |
004 | 07/1.95 | 05.88 | 2.29 | 31.0 | 300 |
003 | 07/2.20 | 06.61 | 2.29 | 33.0 | 200 |
002 | 07/2.47 | 07.42 | 2.29 | 34.0 | 200 |
01 | 19/1.69 | 08.43 | 2.29 | 36.0 | 200 |
1/0 | 19/1.89 | 09.46 | 2.29 | 39.0 | 200 |
2/0 | 19/2.13 | 10.60 | 2.29 | 42.0 | 200 |
5KV EPRN Three Cores Power Cable Refer to ICEA
Conductor | Thickness of | Approx. | Standard | ||
Normative | Number/ | Outer | |||
AWGorMCM | No./mm | mm | mm | mm | M |
008 | 07/1.23 | 03.70 | 2.29 | 27 | 300 |
007 | 07/1.39 | 04.16 | 2.29 | 28 | 300 |
006 | 07/1.56 | 04.67 | 2.29 | 31 | 300 |
005 | 07/1.75 | 05.24 | 2.29 | 32 | 300 |
004 | 07/1.95 | 05.88 | 2.29 | 33 | 300 |
003 | 07/2.20 | 06.61 | 2.29 | 35 | 200 |
002 | 07/2.47 | 07.42 | 2.29 | 36 | 200 |
001 | 19/1.69 | 08.43 | 2.29 | 39 | 200 |
1/0 | 19/1.89 | 09.46 | 2.29 | 42 | 200 |
2/0 | 19/2.13 | 10.60 | 2.29 | 44 | 200 |
3/0 | 19/2.39 | 11.90 | 2.29 | 47 | 200 |
4/0 | 19/2.68 | 13.40 | 2.29 | 53 | 200 |
250 | 37/2.09 | 14.60 | 2.29 | 55 | 200 |
300 | 37/2.29 | 16.10 | 2.29 | 59 | 200 |
350 | 37/2.47 | 17.30 | 2.29 | 62 | 200 |
400 | 37/2.64 | 18.50 | 2.29 | 64 | 200 |
450 | 37/2.80 | 19.60 | 2.29 | 67 | 200 |
500 | 37/2.95 | 20.70 | 2.29 | 70 | 200 |
550 | 61/2.41 | 21.70 | 2.29 | 71 | 200 |
600 | 61/2.52 | 22.70 | 2.29 | 72 | 200 |
650 | 61/2.62 | 23.60 | 2.29 | 74 | 200 |
700 | 61/2.72 | 24.50 | 2.29 | 76 | 200 |
750 | 61/2.82 | 25.30 | 2.29 | 80 | 200 |
15KV EPRN Single Core Power Cable Refer to ICEA
Conductor | Thickness of | Approx. | Standard | ||
Normative | Number/ | Outer | |||
AWGorMCM | No./mm | mm | mm | mm | M |
002 | 07/2.47 | 07.42 | 4.45 | 24 | 300 |
001 | 19/1.69 | 08.43 | 4.45 | 25 | 300 |
1/0 | 19/1.89 | 09.46 | 4.45 | 26 | 300 |
2/0 | 19/2.13 | 10.60 | 4.45 | 28 | 300 |
3/0 | 19/2.39 | 11.90 | 4.45 | 30 | 300 |
4/0 | 19/2.68 | 13.40 | 4.45 | 31 | 300 |
250 | 37/2.09 | 14.60 | 4.45 | 32 | 300 |
300 | 37/2.29 | 16.10 | 4.45 | 34 | 200 |
350 | 37/2.47 | 17.30 | 4.45 | 35 | 200 |
400 | 37/2.64 | 18.50 | 4.45 | 36 | 200 |
450 | 37/2.80 | 19.60 | 4.45 | 37 | 200 |
500 | 37/2.95 | 20.70 | 4.45 | 38 | 200 |
550 | 61/2.41 | 21.70 | 4.45 | 40 | 200 |
600 | 61/2.52 | 22.70 | 4.45 | 40 | 200 |
650 | 61/2.62 | 23.60 | 4.45 | 42 | 200 |
700 | 61/2.72 | 24.50 | 4.45 | 43 | 200 |
750 | 61/2.82 | 25.30 | 4.45 | 44 | 200 |
800 | 61/2.91 | 26.20 | 4.45 | 45 | 200 |
15KV EPRN Three Cores Power Cable Refer to ICEA
Conductor | Thickness of | Approx. | Standard | ||
Normative | Number/ | Outer | |||
AWGorMCM | No./mm | mm | mm | mm | M |
002 | 07/2.47 | 07.42 | 4.45 | 44 | 200 |
001 | 19/1.69 | 08.43 | 4.45 | 46 | 200 |
1/0 | 19/1.89 | 09.46 | 4.45 | 49 | 200 |
2/0 | 19/2.13 | 10.60 | 4.45 | 51 | 200 |
3/0 | 19/2.39 | 11.90 | 4.45 | 54 | 200 |
4/0 | 19/2.68 | 13.40 | 4.45 | 57 | 200 |
250 | 37/2.09 | 14.60 | 4.45 | 60 | 200 |
300 | 37/2.29 | 16.10 | 4.45 | 63 | 200 |
350 | 37/2.47 | 17.30 | 4.45 | 66 | 200 |
400 | 37/2.64 | 18.50 | 4.45 | 68 | 200 |
450 | 37/2.80 | 19.60 | 4.45 | 72 | 200 |
500 | 37/2.95 | 20.70 | 4.45 | 74 | 200 |
550 | 61/2.41 | 21.70 | 4.45 | 77 | 200 |
600 | 61/2.52 | 22.70 | 4.45 | 79 | 200 |
650 | 61/2.62 | 23.60 | 4.45 | 81 | 200 |
700 | 61/2.72 | 24.50 | 4.45 | 83 | 200 |
750 | 61/2.82 | 25.30 | 4.45 | 84 | 200 |
800 | 61/2.91 | 26.20 | 4.45 | 86 | 200 |
5KV EPRN Single Core Power Cable Refer to ICEA
Conductor | Thickness of insulation mm | Approx. Overall Diameter mm | Standard Length M | ||
Normative Cross Area mm2 | Number/ Diameter of Wires No./mm | Outer Diameter Approx. mm | |||
8 | 7/1.2 | 3.6 | 2.29 | 13.5 | 300 |
14 | 7/1.6 | 4.8 | 2.29 | 14 | 300 |
22 | 7/2.0 | 6.0 | 2.29 | 16.5 | 300 |
30 | 7/2.3 | 6.9 | 2.29 | 17.5 | 300 |
38 | 72.6 | 7.8 | 2.29 | 19 | 300 |
50 | 19/1.8 | 9.0 | 2.29 | 20 | 300 |
60 | 19/2.0 | 10.0 | 2.29 | 21 | 300 |
80 | 19/2.3 | 11.5 | 2.29 | 23 | 300 |
100 | 19/2.6 | 13.0 | 2.29 | 24 | 300 |
125 | 19/2.9 | 14.5 | 2.29 | 28 | 300 |
150 | 37/2.3 | 16.1 | 2.29 | 29 | 300 |
200 | 37/2.6 | 18.2 | 2.29 | 31 | 300 |
250 | 61/2.3 | 20.7 | 2.29 | 34 | 200 |
325 | 61/2.6 | 23.4 | 2.29 | 37 | 200 |
400 | 61/2.9 | 26.1 | 2.29 | 40 | 200 |
5KV EPRN Two Core Power Cable Refer to ICEA
Conductor | Thickness of insulation mm | Approx. Overall Diameter mm | Standard Length M | ||
Normative Cross Area mm2 | Number/ Diameter of Wires No./mm | Outer Diameter Approx. mm | |||
8 | 7/1.2 | 3.6 | 2.29 | 26 | 300 |
14 | 7/1.6 | 4.8 | 2.29 | 29 | 300 |
22 | 7/2.0 | 6.0 | 2.29 | 32 | 300 |
30 | 7/2.3 | 6.9 | 2.29 | 33 | 200 |
38 | 72.6 | 7.8 | 2.29 | 35 | 200 |
50 | 19/1.8 | 9.0 | 2.29 | 39 | 200 |
60 | 19/2.0 | 10.0 | 2.29 | 41 | 200 |
5KV EPRN Three Core Power Cable Refer to ICEA
Conductor | Thickness of insulation mm | Approx. Overall Diameter mm | Standard Length M | ||
Normative Cross Area mm2 | Number/ Diameter of Wires No./mm | Outer Diameter Approx. mm | |||
8 | 7/1.2 | 3.6 | 2.29 | 27 | 300 |
14 | 7/1.6 | 4.8 | 2.29 | 31 | 300 |
22 | 7/2.0 | 6.0 | 2.29 | 33 | 300 |
30 | 7/2.3 | 6.9 | 2.29 | 35 | 200 |
38 | 72.6 | 7.8 | 2.29 | 37 | 200 |
50 | 19/1.8 | 9.0 | 2.29 | 41 | 200 |
60 | 19/2.0 | 10.0 | 2.29 | 43 | 200 |
80 | 19/2.3 | 11.5 | 2.29 | 48 | 200 |
100 | 19/2.6 | 13.0 | 2.29 | 52 | 200 |
125 | 19/2.9 | 14.5 | 2.29 | 55 | 200 |
150 | 37/2.3 | 16.1 | 2.29 | 59 | 200 |
200 | 37/2.6 | 18.2 | 2.29 | 64 | 200 |
250 | 61/2.3 | 20.7 | 2.29 | 70 | 200 |
325 | 61/2.6 | 23.4 | 2.29 | 78 | 200 |
15KV EPRN Single Core Power Cable Refer to ICEA
Conductor | Thickness of insulation mm | Approx. Overall Diameter mm | Standard Length M | ||
Normative Cross Area mm2 | Number/ Diameter of Wires No./mm | Outer Diameter Approx. mm | |||
38 | 72.6 | 7.8 | 4.45 | 24 | 300 |
50 | 19/1.8 | 9.0 | 4.45 | 26 | 300 |
60 | 19/2.0 | 10.0 | 4.45 | 28 | 300 |
80 | 19/2.3 | 11.5 | 4.45 | 29 | 300 |
100 | 19/2.6 | 13.0 | 4.45 | 31 | 300 |
125 | 19/2.9 | 14.5 | 4.45 | 32 | 300 |
150 | 37/2.3 | 16.1 | 4.45 | 34 | 200 |
200 | 37/2.6 | 18.2 | 4.45 | 36 | 200 |
250 | 61/2.3 | 20.7 | 4.45 | 39 | 200 |
325 | 61/2.6 | 23.4 | 4.45 | 42 | 200 |
400 | 61/2.9 | 26.1 | 4.45 | 45 | 200 |
15KV EPRN Three Core Power Cable Refer to ICEA
Conductor | Thickness of insulation mm | Approx. Overall Diameter mm | Standard Length M | ||
Normative Cross Area mm2 | Number/ Diameter of Wires No./mm | Outer Diameter Approx. mm | |||
38 | 72.6 | 7.8 | 4.45 | 49 | 200 |
50 | 19/1.8 | 9.0 | 4.45 | 53 | 200 |
60 | 19/2.0 | 10.0 | 4.45 | 55 | 200 |
80 | 19/2.3 | 11.5 | 4.45 | 58 | 200 |
100 | 19/2.6 | 13.0 | 4.45 | 61 | 200 |
125 | 19/2.9 | 14.5 | 4.45 | 66 | 200 |
150 | 37/2.3 | 16.1 | 4.45 | 69 | 200 |
200 | 37/2.6 | 18.2 | 4.45 | 74 | 200 |
250 | 61/2.3 | 20.7 | 4.45 | 81 | 200 |
325 | 61/2.6 | 23.4 | 4.45 | 88 | 200 |
400 | 61/2.9 | 26.1 | 4.45 | 94 | 200 |